Star Delta Starter Wiring Diagram: Power & Control Circuit, Timer and Overload Setting (Pakistan)

Star delta starter wiring diagram guide for 400V three-phase motors in Pakistan: power circuit, control circuit, timer and overload setting

Short answer: a star delta starter wiring diagram has two parts. In the power circuit, the supply goes through an MCCB and the main contactor (KM1) to motor terminals U1-V1-W1, while the other three ends W2-U2-V2 go to a star contactor (KM3) that shorts them together for starting, and a delta contactor (KM2) that connects them back to the three phases for running. In the control circuit, START latches KM1, the star-delta timer holds the motor in star for a few seconds, then drops KM3 and picks up KM2. KM2 and KM3 must never be on together, and the overload relay is usually set to about 0.58 × the motor’s full-load current.

This guide gives you an original power diagram, a control wiring diagram with timer, a sizing chart for contactors and overload, a worked example for a 400V tubewell motor, and the mistakes we see most often in Pakistani panels. Everything here is for 400V three-phase supply from LESCO, MEPCO, FESCO, IESCO or any WAPDA DISCO, or from a generator.

Star delta starter wiring diagram guide for 400V three-phase motors in Pakistan: power circuit, control circuit, timer and overload setting

What a Star Delta Starter Does (in Plain Words)

A three-phase induction motor started direct-on-line (DOL) pulls a big rush of current for the first few seconds. On a weak rural feeder or a generator, that rush makes lights dim, trips the upstream breaker or makes the voltage dip so much that other machines drop out.

A star delta starter cuts that rush by starting the motor with its windings in star (Y). In star, each winding gets 400 ÷ 1.732 ≈ 230V instead of 400V, so the starting current from the line and the starting torque both fall to about one-third of the DOL value. Once the motor has nearly reached full speed, the starter switches the windings to delta (Δ), where each winding gets the full 400V and the motor can give full torque.

PointStar (Y) – startingDelta (Δ) – running
How winding ends are joinedW2, U2, V2 shorted together (star point)U1-W2, V1-U2, W1-V2 (closed loop)
Voltage across each winding≈ 230V400V
Line current≈ 1/3 of DOL starting currentNormal full-load current
Torque≈ 1/3 of DOL starting torqueFull rated torque
Contactors closedKM1 + KM3KM1 + KM2

Check the motor plate first

Star delta starting only works if the motor is designed to run in delta at your supply voltage. On a 400V supply, the nameplate should show something like 400V Δ / 690V Y (some older plates say 380V Δ / 660V Y), and the terminal box must have six terminals. A plate that says 230V Δ / 400V Y means the motor runs in star on 400V; if you try to star-delta it, the windings will see too much voltage in delta and burn. Many small motors are wound this way, so read the plate before you buy a starter.

Star Delta Starter Wiring Diagram: Power Circuit

Star delta starter wiring diagram power circuit: MCCB, main contactor KM1, overload relay, delta contactor KM2, star contactor KM3 and motor terminals U1 V1 W1 W2 U2 V2

Follow the diagram from the top:

  1. Q1 – MCCB or motor-rated breaker. Takes R, Y and B from the supply and protects the whole starter against short circuit. See our MCB vs MCCB guide if you’re not sure which type to use.
  2. KM1 – main contactor. Its output feeds the motor’s start ends U1, V1, W1. KM1 stays closed in both star and delta.
  3. F1 – thermal overload relay. Fitted on KM1’s output, in the leads going to U1-V1-W1. In this position it measures winding (phase) current, not line current, which is why its setting is 0.58 × FLC (explained below).
  4. KM2 – delta contactor. Its line side is tapped from KM1’s output: R, Y, B. Its load side goes to W2, U2, V2. When KM2 closes, R joins U1 to W2, Y joins V1 to U2 and B joins W1 to V2. That is delta.
  5. KM3 – star contactor. Its input is also W2, U2, V2, and its output terminals are bridged together. When KM3 closes, the three winding ends are shorted into a star point.

Remove the factory links from the motor terminal box. All six ends must come to the starter, so you need two 3-core cables (or six single cores) between panel and motor.

Rotation tip: keep the same phase order on KM1 and KM2. If the delta connection is wired the wrong way round, the motor sees a different phase sequence when it changes over; it jerks hard at changeover, draws a big current spike and may trip. Check that the motor turns the same way in star and in delta before connecting the pump or fan.

Star Delta Starter Control Wiring Diagram with Timer

Star delta starter control wiring diagram with timer: stop and start push buttons, KM1 seal-in, timer 15-16 and 15-18 contacts, KM2 and KM3 electrical interlock, 220V coils

Most contactors sold in Pakistan for motor panels have 220V AC coils, so the control circuit is usually taken from one phase and neutral through a small control MCB. If your coils are 400V, take two phases instead. Never mix coil voltages in one panel.

  1. Line → control MCB → overload NC (95-96) → STOP (NC) → START (NO). The overload contact and STOP button are in series, so either one cuts every coil.
  2. KM1 seal-in. A normally open auxiliary contact of KM1 (13-14) is wired across the START button. Once KM1 picks up, it holds itself in after you release START.
  3. Timer KT (A1-A2) is fed from the same latched point, so it starts counting when KM1 picks up.
  4. Star coil KM3 is fed through the timer’s star contact (15-16, closed while timing) and a normally closed auxiliary of KM2.
  5. Delta coil KM2 is fed through the timer’s delta contact (15-18, closes after the time) and a normally closed auxiliary of KM3.

A dedicated star-delta timer opens 15-16 first and closes 15-18 after a short built-in gap, so the star contactor’s arc is out before delta closes. A plain on-delay timer doesn’t give that gap, which is the usual cause of a “bang” and a flashover on changeover. The two NC auxiliaries are the electrical interlock; a mechanical interlock clipped between KM2 and KM3 is the second layer. Use both, because KM2 and KM3 closed together is a dead short across the phases.

Terminal numbers like 15-16-18 are the most common marking, but some timers use different numbers or two separate outputs. Always follow the diagram printed on your timer.

How to Size the Contactors, Overload and Breaker

Star delta starter sizing chart: main, delta and star contactor AC-3 ratings, overload setting 0.58 x FLC and timer setting, with a 28 A motor example

This is where most competitor pages go wrong. They tell you to size every contactor and the overload on the motor’s full-load current (FLC). In a star delta starter, the main and delta contactors only carry the winding current, which is FLC ÷ 1.732 ≈ 0.58 × FLC, and the star contactor carries about one-third of FLC during the start. That’s why star delta starters can use smaller contactors than a DOL starter for the same motor.

PartCurrent it carriesRule
KM1 main contactorWinding currentAC-3 rating ≥ 0.58 × FLC
KM2 delta contactorWinding currentAC-3 rating ≥ 0.58 × FLC
KM3 star contactorStar current (short time)AC-3 rating ≥ 0.33 × FLC
Overload in winding leads (after KM1)Winding currentSet ≈ 0.58 × FLC
Overload in main line (before split)Line currentSet = FLC
MCCB / breakerLine currentAbove FLC, with a curve that doesn’t trip on the start current

Two more points. First, always read the AC-3 rating (motor duty), not the bigger AC-1 number printed for resistive loads. For example, our Schneider LC1D12 is listed at 25A, which is its AC-1 rating; for motor duty it’s a 12A AC-3 contactor. Second, Siemens’ own star-delta starter instructions say the overload in this position should be set to 0.58 times rated motor current and never higher (Siemens operating instructions). Setting it at full FLC there means it will never trip on a real overload.

Worked example: 400V tubewell motor with 28 A on the plate

Say the plate on a submersible or surface tubewell motor reads 400V Δ and 28 A full-load current (this is only an example; use your own plate).

  • Main and delta contactors: 0.58 × 28 = 16.2 A. The next AC-3 size up is 18 A, so a Schneider LC1D18 for KM1 and KM2. If the motor runs long hours in a hot pump room, many panel builders go one size up for margin.
  • Star contactor: 0.33 × 28 ≈ 9.3 A. A 9 A contactor is too tight, so use 12 A AC-3 (LC1D12).
  • Overload relay: after KM1, so choose a range that covers 16.2 A and set the dial to about 16.2 A.
  • Breaker: a motor-rated MCCB or D-curve breaker above 28 A that rides through the star start, for example the 40 A class. Check the trip curve against the motor’s start; our MORA 3-pole MCCB range covers larger motors and sub-main feeds.
  • Timer: start at 6-8 seconds, then measure (see below).
Schneider LC1D18 magnetic contactor 18A AC-3 used as main and delta contactor in a star delta starter

How to Set the Star Delta Timer

The timer should hold the motor in star until it has nearly reached full speed. Switching too early gives almost the same current spike as DOL; switching too late keeps the motor at one-third torque for too long and it heats up.

  1. Set the dial to the starting time on the motor plate if it is given. If not, start with about 6-8 seconds, which is what Siemens’ starter instructions suggest when the time is unknown.
  2. Start the motor with a clamp meter on one phase. Watch the current fall as the motor speeds up, and listen for the hum to settle to a steady pitch.
  3. Note the time it takes to settle, stop the motor and set the timer to that value (a second more is fine).
  4. Restart and check that the changeover is smooth, with only a short kick on the clamp meter.

Pakistan note: motor torque falls with the square of the voltage. On a rural feeder that drops well below 400V in the evening peak, the motor takes longer to speed up in star. If your motor sometimes changes over while still slow, check the voltage at that time before adding more seconds.

Star Delta vs DOL vs Soft Starter vs VFD

MethodStarting current (typical)Starting torqueBest forWatch out for
DOLHighest, often 6-8 × FLCFullSmall motors, strong supplyVoltage dips, breaker trips, belt/coupling shock
Star delta≈ 1/3 of DOL≈ 1/3 of DOLPumps, fans, blowers that start lightNeeds 6 leads and a Δ-400V motor; spike at changeover
Soft starterAdjustable, smooth rampReduced, adjustablePumps where water hammer is a problemHeat in the panel; still full speed only
VFDLowest, close to FLCGood, controlledSpeed control, energy saving, solar pumpingHigher cost, needs correct sizing and filtering

Star delta suits loads that start light: centrifugal pumps, tubewells, cooling-tower fans and big poultry-shed fans. It is a poor choice for loads that need high torque from standstill, such as a loaded conveyor or a compressor that starts against pressure. For more on motor starting basics see motor controller (Wikipedia).

Protection to Add in Pakistani Conditions

  • Phase failure and low/high voltage: a missing phase or very low voltage burns more motors than overload does. A three-phase protector such as the MORA 100A 3 phase voltage and current protector cuts the supply when a phase drops or voltage goes out of range.
  • Load-shedding restarts: with START/STOP push buttons and a seal-in, the motor will not restart by itself when power returns. That is safer. If you replace the buttons with a float switch, pressure switch or timer for automatic running, add a restart delay so every motor on the line doesn’t start at the same moment when power comes back.
  • Generator supply: a star delta starter makes life easier for the generator, but the changeover kick is still there. Size the generator for the motor plus the rest of the load.
  • Earthing: earth the panel body, the motor frame and the cable armour. Metal pump rooms with wet floors are high-risk.

If you are building a full panel for fans, see our exhaust fan control panel guide, and for single-phase motors and appliances, read protection devices for ACs, motors and fridges.

Common Star Delta Faults and What They Mean

SymptomLikely causeWhat to check
Bang or flash at changeoverNo gap between star and delta; plain timer usedUse a proper star-delta timer; check interlocks
Big kick and trip at changeoverTimer too short or delta phase order wrongMeasure run-up time; check U1-W2, V1-U2, W1-V2
Motor hums in star, won’t speed upPhase missing, very low voltage or load too heavyVoltage on all 3 phases; pump/valve condition
Overload trips after a few minutes in deltaOverload set too low, or motor really overloadedClamp current vs 0.58 × FLC per lead
Overload never trips, motor burnsOverload set at full FLC in winding leadsReset to 0.58 × FLC
Motor stops when START is releasedSeal-in contact not wired or wrong (NC used)KM1 13-14 across START

Installation Checklist

  • Motor plate says Δ at 400V and has six terminals; factory links removed.
  • Contactors chosen by AC-3 rating: main and delta ≥ 0.58 × FLC, star ≥ 0.33 × FLC.
  • Overload placed after KM1 and set to 0.58 × FLC (or FLC if it’s in the main line).
  • Coil voltage matches the control supply (220V or 400V); control MCB fitted.
  • Electrical interlock (KM2 NC in KM3 coil line, KM3 NC in KM2 coil line) plus mechanical interlock.
  • Proper star-delta timer, set by measured run-up time.
  • Same rotation in star and delta checked with the load uncoupled.
  • Phase failure / voltage protection and good earthing.
MORA 3-pole MCCB used as the main breaker ahead of a star delta starter panel

FAQs

Which HP motor needs a star delta starter?

There’s no single number in Pakistan. Advice online ranges from 5 HP to 15 HP and up, and some DISCOs or factory owners set their own limit. As a practical rule, think about star delta (or a soft starter or VFD) once DOL starting dims the lights, trips breakers or strains the generator. The motor must also be a 400V-delta, six-lead motor.

Why is the overload set at 0.58 of the motor current?

Because in the usual star delta wiring the overload sits in the leads to U1-V1-W1, which carry winding current, not line current. Winding current is line current ÷ 1.732, which is 0.58 × FLC. If the overload sits in the main line before the split, set it to the full FLC instead.

What is the timer setting for a star delta starter?

Set it to the time the motor takes to reach nearly full speed. If you don’t know that yet, start with 6-8 seconds, then measure with a clamp meter and adjust. Light pumps and fans often need less; heavy fans with big blades often need more.

Can I use 220V coil contactors in a star delta starter?

Yes. Most contactors sold for motor panels in Pakistan have 220V coils. Feed the control circuit from one phase and neutral through a control MCB. Just make sure the timer and all three contactors use the same coil voltage.

Star delta starter motor kyun garam hota hai?

The most common reasons are: the timer is too long, so the motor stays in star at low torque; the overload is set wrong; one phase is weak or missing; or the load is heavier than the motor rating. Check the voltage on all three phases, the timer setting and the running current in each lead.

Need Parts or a Panel Checked?

HN Electric supplies genuine magnetic contactors, MCCBs, three-phase protectors and panel parts across Pakistan. Send a photo of your motor nameplate and your panel on WhatsApp 0329 1654950 and we’ll suggest the right contactor sizes, overload range and protection. Motor ki plate ki photo bhejein, hum sahi starter parts bata denge.

author-avatar

About Mehmood Ali

Mehmood Ali writes product and buying guides for the HN Electric blog, covering circuit breakers, surge and voltage protection, changeover switches, automatic transfer switches and solar equipment. His articles help customers compare product specifications and available options. HN Electric is based in Valencia, Lahore and supplies electrical and solar products across Pakistan. Electrical installation and system modifications require assessment by a qualified professional.